Keeping people, investments, and the environment safe from Flammable or Hazardous Materials
AH 4-hour rated UL DES U419 / MEA 81-98-M walls & ceilings Class 1, Division 2 Compliant
Drum Capacity: 27
Pallet capacity 48" x 40": 8
Sump Capacity: 540.42 gallons
Wind Force Rating: 150mph
Side Door opening: 18'8" wide x 7' tall
End door opening: 7'8" wide x 7' tall
Exterior dimensions: 20ft long x 8ft wide x 8.5ft tall ISO container
Interior dimensions: 18' long x 6'9" wide x 7'2" tall (6'2" Floor to bottom of the light)
GVW: 13,500 pounds
GVWR: 60,190 pounds
Liquid gallon capacity: 1,800 gallons
Lockable and Weatherproof Construction.
14-gauge corrugated steel
4 top and bottom 4 bottom crane pad eyes
Forklift pockets
Pryo Chem Monarch PCI-35ABC Dry Chemical Total Flooding Fire Suppression System. Equipped with an external remote pull station, external audible alarm, and control head micro switch which cut power to the exhaust fan when the system has been activated. Design to meet or exceeds NFPA Code 17- (Standard for Dry Chemical Extinguishing Systems), and NFPA 30-(Flammable and Combustible Liquids Code) Specifications.
Canarm non-sparking Explosion-Proof Enclosed Exhaust Fan – 12in giving 1,640 CFM which exceeds NFPA 30.18.6.6.1 & NFPA 30.18.6.2.
Built-in secondary Security 6in deep steel floor sump for spill containment
Floor grading support beams at 1 ft on Center.
Galvanized grading is rated at 850 pounds per square foot.
Removable Steel non-skid Floor Grating Provides Full Access to Secondary Containment
Interior Explosion Proof Lighting Class 1, Division 2
3-Hour Fire-Rated vent fire dampers meet or exceed NFPA 30 & NFPA 5000
All applicable placards and stickers that include: No Smoking within 50 feet, NFPA diamond, NPPA Aluminum Flip File Placard, 10-Legend Worded Set, intended use Warning sticker, Warning Over Hang sticker.
Premium, high-solids formula with acrylic polymers, resins, fillers, and titanium dioxide pigments white outside paint coating that Reflects 92% of solar heat and rays for a cooler inside temp.
All vent openings are equipped with three hours, UL Listed fire dampers, and foul weather hoods.
Static Grounding system
220V, Single-Phase 50-amp Electrical requirement. We will provide a female S.O plug to connect directly to the unit's power panel. The unit must also be properly grounded by connecting a green ground wire coming out of the power panel to an 8' copper grounding rod which must be driven down 95% in the ground. Each unit will be provided one grounding rod.
Built to comply with NFPA Code 17, 17A, 30, and 70 Specifications. Approved holding of hazardous and flammable materials in accordance with local regulations.
Side-Door / 2 Large Doors
External Back Wall Layout
Interior Fire Suppression System Layout
4 Large Doors Exposing a 19’ Opening
Left Side
National Fire Protection Association
Occupational Safety and Health Administration
To learn more about our 20’ Open Side / 4-hr-Rated Portable Flammable / Hazmat Container please contact us.